The exhaust terminal shall beat least 1 ft above grade and placed in such a location where the exhaust terminal is not susceptible to blockage from debris, leaves or falling snow or ice from roofs. A 1/2" wire-mesh screen at the exhaust terminal must be maintained in good working order.
9.

The exhaust terminal shall terminate more than 3 ft from any other building opening, oil tank vent or oil tank fill inlet. (6 ft from any gas service regulator vent outlet. Guidelines for the location of the intake air terminal


Separate air intake hood and aerocowl exhaust termination
Advise owner to keep intake and exhaust terminations free of debris and snow.
Burner settings