Installation Manual for Buderus G115 Direct Vent Oil Boilers



Download 108.99 Kb.
View original pdf
Page3/25
Date06.01.2019
Size108.99 Kb.
1   2   3   4   5   6   7   8   9   ...   25
1.

The exhaust terminal must be located such that the products of combustion will be freely dispersed outside without reentering the building. The exhaust gases shall not interfere with people, overheat combustible materials, or enter adjacent buildings.
2.

Exhaust terminal shall beat least 2 ft from an adjacent building.
3.

The exhaust terminal shall beat least 7 ft above grade when above public walkways.
4.

The exhaust terminal shall not be located underneath a porch or crawlspace.
5.

The exhaust terminal shall not be located less than 3 ft from an L-shaped inside building corner and no less than 3 feet away from an outside corner.
6.

The exhaust terminal shall be located at least 3 ft above any forced air inlet within 10 ft horizontally.
7.

The exhaust terminal shall not be less than 4 ft below, 1 ft above, or 4 ft horizontally from any door, window or gravity air inlet into the building.


Separate air intake hood and aerocowl exhaust termination
Advise owner to keep intake and exhaust terminations free of debris and snow.
Burner settings
G115/21 riello bf