  • NOTE
1.

Oil pump pressure should be 140 - 150 psi for the Riello BF burners 140 - 150 psi for the Carlin P burners. Make adjustments if necessary.
2.

Adjust the air set to get a CO value of 11.0% – 12.5% with 0 smoke #. Perform final test with all covers and inlet piping in place.

NOTE: Stop burner operation at once if smoke emerges from the exhaust terminal. Check and make necessary burner adjustments to obtain smoke-free flue products.
NOTE: MAKE SURE the burner observation port located on the burner door is sealed airtight by properly tightening the port screw. Use extra sealant if necessary.
NOTE: Affix the transparent blank cover label over the boiler rating plate. Affix the electrical and clearance label on the boiler jacket near the boiler rating plate.